At the end of the Switch Operation Menu is the Loop Check function. Using the MODE key
to select the Loop Check function. After lop is displayed for 1 second, the value of the lat-
est measurement mode is displayed as default. Use   keys to set displayed value any-
where between –1999 and 1999 to confirm switch operation and/or analog output operation.
#!$#"
);1+3-A78-:)<176;
In all setting modes, values are set with the keys. Use the key to increase and
the  key to decrease the value. A repeat state occurs in three phases of speed when the
  keys are pressed for more than 0.5 seconds to increase or decrease numerical value.
 keys are also used for setting switch, unit and filter in the function setting mode.
!-(-:77."-6;7:
In measurement mode, select display to adjust zero using key. Press MODE + keys for
more than 3 seconds (unit “---” display blinks) after releasing pressure from the pressure port.
Automatic zero adjustment takes place approximately 1 second later for pressure display to
be zero.
When the zero adjustment is successful, Adj is displayed.
Error displays e-0 for 1 second when applied pressure was outside of range of –10 to 10%
FS, zero adjustment will not be allowed.